EK1501 Beckhoff EtherCAT Coupler With ID Switch 24VDC Terminal Modules Up To 65,534
1.Overview of the EK1501 Beckhoff
2.Core Features:
1. Core Tasks
Connect EtherCAT Terminals (ELxxxx) to a 100BASE-FX fiber optic network, enabling ultra-long-distance, interference-resistant distributed I/O stations.
Converts upper-layer Ethernet messages into E-bus signals, automatically mapping the complete process image without configuration.
2. Key Parameters
1. Network and Topology
Protocol: EtherCAT
Transmission Medium: Single-mode glass fiber 9/125 µm (SC-Duplex)
Rate: 100 Mbit/s, hardware forwarding delay ≈ 1 µs
Inter-station distance: ≤ 20 km
Number of terminals connectable to a single network: ≤ 65,534, Addressable I/O points: 4.2 GB
Address/Topology: 3-digit hexadecimal ID with 4,096 groups configurable, allowing for flexible configuration of line, star, or mixed structures.
2. Power Supply and Consumption
System Power Supply (US): 24 V DC (-15% / +20%)
Field Power Supply (UP): 24 V DC, power contacts, maximum 10 A
US consumption: Typical 150 mA + (∑ E-bus current / 4)
E-bus power supply: 5 V / 2 A (internal), can be expanded using a feeder module such as the EL9410
Electrical isolation: 500 V (power / contacts / Ethernet)
3. Mechanical and Environmental
Dimensions: 51 × 100 × 69 mm (W × H × D), DIN-35 rail mountable
Weight: ≈ 190 g
Protection rating: IP 20, mounting position optional
Operating temperature: -25 … +60°C; Storage: -40 … +85°C
Humidity: 95% RH, non-condensing
Vibration/shock resistance: Complies with EN 60068-2-6 / 2-27
EMC: EN 61000-6-2 (Immunity) / EN 61000-6-4 (Emission)
Certifications: CE, UL, CCC, ATEX, IECEx
Ex Marking: II 3 G Ex ec IIC T4 Gc / Ex ec IIC T4 Gc, suitable for use in Zone 2 explosive gas environments
3. Main Features
20 km cascading of single-mode fiber, saving repeater and fiber optic cable costs
Hardware-based real-time forwarding with a period jitter of < 1 µs, enabling high-speed closed-loop control
Built-in 2 A E-bus power supply, capable of directly driving 30-40 standard digital terminals
3-digit ID dial for device grouping, quick location, and hot-swappable maintenance
Independent system/field power supply, supporting mixed-voltage I/O modules
Wide operating temperature, vibration resistance, and electromagnetic interference resistance make it suitable for demanding applications such as power generation, oil and gas, rail transit, and tunnels
Configuration-free plug-and-play: TwinCAT automatically identifies topology and terminal models, ensuring zero-programming during commissioning
EK1501 (multimode 2 km) and EK1501-0010 (single-mode 20 km) has the same parameters except for the fiber specifications and distance. Users can freely choose according to the wiring environment.
The EK1501 fiber optic coupler is suitable for a variety of industrial automation scenarios:
Widely distributed systems: These include wind farms and large production lines, where long-distance, interference-resistant communication is critical.
Environmentally sensitive to electromagnetic interference: Fiber optic communication is inherently immune to electromagnetic interference, making it suitable for use in environments such as high-voltage facilities and welding equipment.
Systems requiring flexible topologies: These include automated production lines requiring complex wiring configurations such as star and tree topologies.
Applications requiring high scalability: These include large machinery or process control systems requiring a large number of distributed I/O points.
3.Product details pictures
![]()
![]()
4. Related products
| EK1110 | EK1122 |
| EK1818 | EK1100 |
| EL1008 | EL2008 |
| EL1088 | EL2088 |
| EL1904 | EL2904 |
| EL3002 | EL3004 |
| EL3052 | EL3062 |
| EL3152 | EL3162 |
| EL3202 | EL3204 |
| EL3356 | EL3453 |